    您當前的位置:首頁 > 技術文章 > Common faults and causes of zirconia oxygen analyzers

    Common faults and causes of zirconia oxygen analyzers

    發布時間: 2024-12-13  點擊次數: 574次

    1. System maintenance.

    If the oxygen indicator shows zero or no oxygen indication in the oxygen quantity converter, first check whether the oxygen indication circuit open. If the circuit is normal, check whether the zirconia probe is normal. At a temperature of 700℃, measure the DC millolt value of the oxygen cell. If the potential is greater than 1 millivolt and the resistance is greater than 100Ω, it indicates the probe is aged and needs to be replaced with a sensor or probe. If the potential is less than 1 millivolt and the resistance is less than100Ω, it indicates an open circuit in the wiring, which should be checked and handled one by one.

    2. constant temperature system failure.

    (1) If the heating temperature cannot be maintained, check whether there is a short circuit or open circuit in the resistance wire inside the heating furnace The normal resistance of the heating furnace wire is about 60-80Ω. If the resistance wire is open or the resistance measured by the multimeter less than 60Ω, the heating furnace wire should be replaced.

    (2) When the converter shows that the temperature is too high or out of control, it not only causes inaccurate oxygen display but also acceler the aging or damage of the zirconia head. At this point, you should immediately check if the thermocouple is open-circuited, or a multimeter to check the thermocouple. If the resistance is greater than 20Ω, it is judged that the thermocouple is open-cuited, and the thermocouple and zirconia head should be replaced; another reason for the temperature失控is: relay or temperature control circuit failure, relay or temperature control circuit failure will cause the oxygen converter to always be in one of the heating voltages of the heating furnace, thus leading to an increase in.

    3. oxygen cell fault.

    (1) After the oxygen cell has been used for a period of time, the contact points of its leads may become oxidized, resulting in contact or detachment. This can cause the Em value (in units of a multimeter) to fluctuate and become unstable. Observe the oxygen cell and take action.

    (2) When the oxygen signal deviation is too large or inaccurate, it may be due to a short circuit in the zirconia electrode, which case the wiring of the zirconia cell should be checked for short circuits. When the temperature does not rise, if the internal resistance is less than 0Ω, it indicates a short circuit in the electrode, and the zirconia head needs to be replaced.

    (3) During the operation of the oxygen measurement device, if the background potential exceeds 10mV or is less than -30mV, it must be recalibrated. If the background potential remains abnormal after calibration, it indicates that the probe has aged and can no longer be used.

    4. pneumatic circuit failure.

    (1) The zirconia head is clogged with ash, causing an obstruction in the reference gas circulation. This results in a decrease in probe output potential Em and an increase in the background potential Eo. In this case, blowing several times with a bulb syringe at the gas inlet of the will resolve the issue after the gas line is unclogged.

    (2) Oxygen cell ash blockage: The probe should be removed from the ash blockage and the filter should be reinstalled.

    (3) Probe leakage has a significant impact on the probe.

    5. The oxygen content on both sides of the boiler is too high.

    By adjusting the boiler combustion conditions, when starting or stopping the boiler fan or coal mill group, if the oxygen content deviation on both sides of the boiler is large, it is a normal phenomenon. Once the boiler combustion conditions stabilize, the oxygen content display will return to normal. If the unit adjustment is not in place and the deviation is large on both sides, it is necessary to check if the zirconia head is working properly by dismantling the transmitter for inspection. The device requires the operator to adjust the gas flow. The gaseous and reference state gases should continuously flow through the electrode without stopping, and there should be no dead ends. However, too large a flow will have a cooling effect, making the cell temperature uneven and causing errors. If the flow is too small, it is not only easy to form stagnant gas flow and dead zones but also may cause local changes in oxygen concentration due to the conduction of oxygen ions, thus affecting the accuracy of the measurement and causing deviations on both sides.

    6. On-site interference causes failures.

    For newly installed instruments, due to the strong electromagnetic field, when an unstable fault occurs, the first thing to consider is the interference issue.


在線客服 聯系方式 二維碼

服務熱線

0550-2409223

掃一掃,關注我們

皖公網安備 34118102000850號

主站蜘蛛池模板: 亚洲春色在线视频 | 欧美护士激情第一欧美精品 | 久久久亚洲欧洲国产 | 国产一区国产二区国产三区 | 日本老年人精品久久中文字幕 | chinese调教在线播放 | 综合欧美日韩一区二区三区 | 中文字幕日韩精品亚洲七区 | 欧美一区二区在线观看视频 | 视频办公室添的我好爽 | 在线国产资源 | 99久在线精品99re6视频 | 一级做性色a爱片久久片 | 亚洲国产情侣一区二区三区 | 国产精品每日在线观看男人的天堂 | 日本特级黄毛片毛片视频 | 免费精品99久久国产综合精品 | 国产丝袜美腿高跟白浆 | 国产欧美在线观看不卡 | 欧美成人手机视频 | 不卡一级毛片免费高清 | 色屁屁影院在线观看 | 日本特黄aaaaaaa大片 | 伊人影院视频 | 黄色片xxx | 国产视频一区二 | 免费摸碰碰视频在线观看 | 国产一级做a爰片在线看免费 | 日本高清在线一区二区三区 | 正在播放国产会所按摩视频 | 国产在线精品一区二区 | 久久国产欧美日韩精品免费 | 免费看污污网站 | 国产精品国产三级国产 | 国产一级高清免费观看 | 精品亚洲一区二区 | 免费一级大毛片a一观看不卡 | 黄色片免费网站 | 天天色播 | 欧美特黄三级在线观看 | 亚洲成在人天堂一区二区 |